Underfloor heating with Devi InControl in Home Assistant

Devi InControl floor thermostat installed as a replacement for a Devi 233. The floor sensor can be reused.

The purpose of this setup has been to integrate electric underfloor heating into a unified Home Assistant setup, where heating can be controlled and coordinated together with other heat sources and overall energy consumption.

The starting point is an underfloor heating system from DEVI, controlled by a Devi InControl floor thermostat, which can communicate via Zigbee and be integrated directly into Home Assistant. Devi InControl can directly replace the Devi 233, which is a widely used thermostat in a 1½ Fuga module in Danish underfloor heating systems. The replacement must be carried out by a licensed electrician and only takes a few minutes.

Manufacturer’s recommendation: DEVI Connect

DEVI recommends using DEVI Connect as the Zigbee gateway for Devi InControl thermostats. DEVI Connect acts as the manufacturer’s official link between the thermostats, the app, and cloud services.

In this setup, DEVI Connect has deliberately been omitted. Devi InControl can be paired directly with Home Assistant via Zigbee, making it possible to avoid additional hardware and a parallel control system.

See the manufacturer’s official installation guide for Devi InControl (PDF), which also contains information on how to switch to Zigbee mode.

Integration with Home Assistant

Via Zigbee, Devi InControl can be paired directly with Home Assistant, for example via ZHA. In one case, where the thermostat was far from the Zigbee dongle (productlink), I had to use a 5-meter USB extension cable to make the pairing succeed.

In Home Assistant, the underfloor heating appears as a standard thermostat with current temperature, adjustable setpoint, and centralized display and control. Communication is local and without cloud dependency.

The built-in minimum limit

According to the manufacturer’s documentation, Devi InControl can be set down to 5 °C when the thermostat is used with a floor sensor.

In this installation, and with the firmware version installed on the Devi InControl thermostat, it has not been possible via ZHA to set the setpoint directly below 15 °C. Attempts to set a lower setpoint, for example 6 °C, resulted in the thermostat jumping back to 15 °C, even though the thermostat was configured with a floor sensor. This temperature is too high in an unoccupied summer house during winter due to energy consumption, and it is precisely in summer houses that electric heating is particularly common.

Setpoint below 15 °C – a two-step workaround

In practice, however, it was possible to bring the thermostat below 15 °C by changing the setpoint in two phases via Home Assistant. First, the setpoint is set to 15 °C, and shortly after it is set to the desired low value, for example 6 °C. This two-step change was accepted by the thermostat, whereas a direct jump to 6 °C was not. The workaround therefore requires the setpoint change to be handled as a small sequence in the automation, typically with a short delay between the two steps. In practice, this made it possible to significantly reduce underfloor heating during periods without use, without being locked to 15 °C as a minimum.

About coding

This case describes experience and architecture, not specific Home Assistant automations. The implementation of the two-step change depends on the specific installation. Automations can be generated using AI once the necessary technical prerequisites are known.